NEC conduit fill calculator
Conduit fill is the total cross-section of the conductors divided by the internal area of the raceway. NEC Chapter 9 Table 1 allows 53% for one conductor, 31% for two and 40% for three or more, grounds included1. Four 10 AWG THHN take 0.0844 in² of the 0.533 in² inside 3/4 in EMT, a 15.8% fill, well under 40%.
Within the limit for 3/4 in EMT.
| Conductors | 4 |
| Conductor area | 0.0844 in² |
| Raceway area (100%) | 0.533 in² |
| Allowed area (40%) | 0.2132 in² |
Smallest EMT that works: 1/2 in.
The rules behind the number
- Fill limits by number of conductors: 53% for one, 31% for two, 40% for more than two.12
- Equipment grounding and bonding conductors count toward fill, at their actual size (Chapter 9, Note 3).1
- Nipples 24 in or shorter between boxes or enclosures may be filled to 60% (Chapter 9, Note 4).1
- When every conductor is the same size, a calculated maximum of x.8 or more may be rounded up to the next whole conductor (Chapter 9, Note 7). Annex C tables already include that rounding; this calculator checks the fill percentage directly.1
- Fill isn't ampacity. More than three current-carrying conductors in a raceway need the adjustment factors in 310.15(C)(1), which may push you to a larger wire before fill does.2
Fill % = (sum of conductor areas, Table 5) ÷ (raceway area, Table 4) × 100
Allowed area at 40%, by raceway
| Trade size | EMT | PVC Schedule 40 | RMC (rigid metal conduit) | IMC | PVC Schedule 80 |
|---|---|---|---|---|---|
| 1/2 in | 0.122 | 0.114 | 0.126 | 0.137 | 0.087 |
| 3/4 in | 0.213 | 0.203 | 0.220 | 0.234 | 0.164 |
| 1 in | 0.346 | 0.333 | 0.355 | 0.384 | 0.275 |
| 1-1/4 in | 0.598 | 0.581 | 0.610 | 0.659 | 0.495 |
| 1-1/2 in | 0.814 | 0.794 | 0.828 | 0.890 | 0.684 |
| 2 in | 1.342 | 1.316 | 1.363 | 1.452 | 1.150 |
| 2-1/2 in | 2.343 | 1.878 | 1.946 | 2.054 | 1.648 |
| 3 in | 3.538 | 2.907 | 3.000 | 3.169 | 2.577 |
| 3-1/2 in | 4.618 | 3.895 | 4.004 | 4.234 | 3.475 |
| 4 in | 5.901 | 5.022 | 5.153 | 5.452 | 4.503 |
Conductor areas
| Size | THHN / THWN-2 | XHHW / XHHW-2 |
|---|---|---|
| 1 AWG | 0.1562 | 0.1534 |
| 2 AWG | 0.1158 | 0.1146 |
| 3 AWG | 0.0973 | 0.0962 |
| 4 AWG | 0.0824 | 0.0814 |
| 6 AWG | 0.0507 | 0.0590 |
| 8 AWG | 0.0366 | 0.0437 |
| 10 AWG | 0.0211 | 0.0243 |
| 12 AWG | 0.0133 | 0.0181 |
| 14 AWG | 0.0097 | 0.0139 |
| 250 kcmil | 0.3970 | 0.3904 |
| 300 kcmil | 0.4608 | 0.4536 |
| 350 kcmil | 0.5242 | 0.5166 |
| 400 kcmil | 0.5863 | 0.5782 |
| 500 kcmil | 0.7073 | 0.6984 |
| 1/0 AWG | 0.1855 | 0.1825 |
| 2/0 AWG | 0.2223 | 0.2190 |
| 3/0 AWG | 0.2679 | 0.2642 |
| 4/0 AWG | 0.3237 | 0.3197 |
From the takeoff to the conduit schedule
Conduit sizing usually happens after the count: once you know how many circuits leave a panel and how they group into home runs, fill decides the trade size and the trade size drives material and labor. The device and fixture count is the input; that part AmpCount does from the legend, and the electrical takeoff guide explains how the counted and measured halves fit together. For long runs, check the voltage drop before settling the wire size.
Feeder conduits follow from the service and feeder sizes, so on design-build work the electrical load calculation worksheet comes first. At the other end of the run, the conductors you put in the pipe also land in a box, and the NEC box fill check tells you whether that box needs to grow too.
A larger trade size changes more than the pipe: fittings, straps, supports and the labor per 100 ft all step up with it. The Excel estimate template prices conduit per 100 or per 1,000 ft, with a separate labor unit for each size. On jobs with hundreds of runs, that is the work estimating suites for commercial work handle with conduit assemblies.
More calculators and guides
Sources
- NFPA 70 revision cycle, Code-Making Panel 8 public input responses (quotes 2023 Chapter 9 Table 1, Percent of Cross Section of Conduit and Tubing for Conductors and Cables, and its Notes to Tables)
- NFPA 70, National Electrical Code, 2023 edition (read online at nfpa.org)
- NEC Chapter 9 Table 4, conduit dimensions and percent area (NECA-IBEW reprint)
- NEC Chapter 9 Table 5, conductor dimensions (NECA-IBEW reprint)
NFPA 70 and National Electrical Code are registered trademarks of the National Fire Protection Association. AmpCount is not affiliated with NFPA.